G Grizzly Backflow & Plumbing
Amelia, LA · 70340 Local testers · Utility reports filed

Double Check Valve Testing in Amelia, LA Near Me

Double check valve assembly testing in Amelia, LA for low-hazard and fire line connections. Call (833) 990-5874 to schedule.

Double Check Valve Testing in Amelia, LA
Call us
(833) 990-5874
Certified testers
Reports filed with your utility
RPZ, DCVA and PVB
Price talked through by phone

Double Check Valve Testing in Amelia, LA

A double check valve assembly, or DCVA, has two independent spring-loaded checks between two resilient-seated shutoffs and four test cocks. It is approved for low-hazard connections, so you see it on many fire lines, apartment services and some irrigation systems.

The tester bleeds and reads each check separately. Each one has to hold a differential of at least 1.0 psid. If a check reads lower, the cause is usually a worn rubber disc, a weak spring or debris across the seat.

Unlike an RPZ, a DCVA can be installed in a pit or vault in many jurisdictions, which brings its own problems. Flooded vaults make test cocks hard to reach and corrode the bolts. Testers often pump the vault before they can start.

Grizzly Backflow & Plumbing connects you with local testers in Amelia, LA for double check valve testing, report filing with your purveyor and repair if a check fails. Good backflow prevention depends on both checks holding, not one. Call (833) 990-5874.

How it works

Four steps to backflow testing in Amelia, LA

  1. 01

    Grab your notice

    Have the utility letter handy. It lists the device, serial number and due date.

  2. 02

    Talk it through

    Call (833) 990-5874. We go over the device type and the price before anything is booked.

  3. 03

    Test day

    A certified tester reads each check and the relief valve on a calibrated gauge.

  4. 04

    Report filed

    The report goes to your water utility, and you keep a copy for your records.

Coverage

Backflow Testing Services Across Amelia, LA

Backflow testing for the neighborhoods and ZIP codes around Amelia, LA.

ZIP codes we serve

70340

Backflow testing FAQs

Questions about backflow testing

Questions we hear most often about Double Check Valve Testing in Amelia, LA.

Talk to a person
Will my water be off during the test?
Yes, briefly. The tester closes the shutoff valves on the assembly while reading the checks, so water downstream of the device is off until the test is done.
Can a backflow preventer freeze?
Yes. Trapped water expands and can crack the bronze body or blow out the bonnet. Insulated enclosures, heat cable or draining the device for winter prevent it.
Do I need an expansion tank after installing a backflow preventer?
Often, yes. The device makes your plumbing a closed system, so heated water cannot expand back to the main and the water heater relief valve may start dripping.
What is a cross-connection?
Any point where drinking water piping can come into contact with a non-potable source. Common examples are a hose in a bucket, a boiler fill line and an irrigation system.
Is fire sprinkler backflow testing different?
Yes. Along with the standard check valve test, NFPA 25 calls for an annual forward flow test on fire line backflow assemblies. Results often go to both the water utility and the fire authority.